SmartWall Specifications
SPECIFICATIONS
The high performance concrete masonry units in the SmartWall shall exceed the requirements of ASTM C 90 PLUS have the following improvements:
Shrinkage:
.065 maximum per ASTM C 426
Concrete Unit Weight:
Maximum Concrete Unit Weight (Density) of 93 Ibs /ft3 (1,500 kg/M3) Oven Dry
Quality Assurance:
Compliance with this specification shall be assured with testing in accordance with ASTM C 140,"Test Method of Concrete Masonty Units." The SmartWall unit manufacturer shall certify that the SmartWall units provided meet the specifications.
Strength:
Minimum Compressive Strength of 2500 psi (20 MPa) Net Area Strength
Performance:
Fire- Two, three and four-hour ratings available. Contact the SmartWall supplier.
Insulation- Values based on NCMA TEK 6-2A (1996)

ASTM Standards- Must exceed all pertinent standards.

SmartWall Units - Weight:
Maximum Jobsite  Weight (Mass) of SmartWall Units (1)
Size Not to Exceed
4" x 8" x 16" 18 lbs. ( 8.0 kg )
6" x 8" x 16" 23 lbs. ( 10.5 kg )
8" x 8" x 16" 26 lbs. ( 11.5 kg )
10" x 8" x 16" 33 lbs. ( 14.5 kg )
12" x 8" x 16" 36 lbs. ( 15.5 kg )
8" x 8" x 24" 38 lbs. (17.0 kg )